比較以簡易濾膜法及傳統方法偵測空調冷卻水塔中退伍軍人桿菌盛行率之有效性-+-Legionella pneumophila from cooling tower in Taipei: Prevalence, Epidemioiogical Analysis, and Comparison of the effectiveness of Detteetion Methods and Disinfectants

-+-

檔案

本條目沒有附加檔案。

日期

類型

系所

摘要

從1997年7月至1998年6月,在台北市611個不同的地點,使用輕便型的可充電式水檢體採集機、一次性可丟棄式的過濾裝置,以及含cephalothin, colistin, cycloheximide, vancomycin(CCVC)之BCYEα培養基進行嗜肺退伍軍人桿菌(Legionella pneumophila)的環境流行病學調查,在403棟獨立大樓中,145棟為陽性,檢出率為35.0%;在618個冷卻水塔中,169座為陽性,檢出率為27.9%。若依據各種性質不同的大樓,包括公家機關辦公大樓、醫院、私人大樓、學校、戲院、飯店、百貨超市以及KTV(MTV)進行分析,發現其檢出率分別為38.9%(63/162)、48.4%(30/62)、25.0%(19/76)、39.3%(11/28)、25.6%(7/27)、13.3%(2/15)、30.4%(7/23)以及42.9%(6/14),其中以醫院檢出率為最高, MTV(MTV)次之;若根據冷卻水塔進行分析,各性質大樓檢出率依序為30.4%(72/237)、39.6%(36/91)、16.4%(23/140)、28.9%(13/45)、24.2%(8/33)、15.0%(3/20)、21.1%(8/38)及40.0%(6/15)。其中以KTV(MTV)檢出率最高,醫院次之。進一步分析所分離之退伍軍人桿菌菌種,發現86.3%(177/205)為嗜肺退伍軍人桿菌(Legionella pneumophila),其中以血清群第一型(Lpneumophila serogroup 1)佔59.3%(105/177)。為了尋求一種適合一般檢驗室的偵測退伍軍人桿菌方法,本研究亦比較離心法和過濾法之退伍軍人桿菌檢出率,當以等量之50~500 ml水檢體進行操作時,離心法所分離之總生菌數(Legionella spp.加上雜菌)和Legionella spp.數目高於過濾法,但因過濾法可過濾1,000~2,000ml水檢體,若與只使用50ml水檢體的離心法比較時,則過濾法所獲得的總生菌數為離心法之9.7~23.3倍,而Legionella spp.為7.8~22.2倍。同時,在調查過程中發現全部的冷卻水塔檢體可之過濾量均超過200ml以上,其中大於1,000ml過濾量之檢體數佔全部檢體之78.6%(486/618)。
由於過濾檢體量的多寡反映水塔的清潔與否,本研究發現當檢體量為1000~2,000ml,嗜肺退伍軍人桿菌(Legionella pneumophila)檢出率為26.5%(129/486),檢體量為500~1000ml檢出率為29.2%(24/82),而檢體為200~500ml之檢出率最高,達33.3%(16/48),此顯示不常清洗的骯髒水塔出現嗜肺退伍軍人桿菌的比例較高;本調查亦對曾分離出嗜肺退伍軍人桿菌的陽性冷卻水塔在消毒及清洗後進行複查,發現大樓檢出率為2.8%(1/36),而水塔檢出率為4.1%(2/49),至於在陰性水塔追蹤方面,第一次檢驗後三個月進行複檢,只有一個水塔檢驗出,檢出率為6.7%(1/15),而六個月後進行複檢,檢出率為6.4%(6/94),因此,冷卻水塔可以每隔六個月做一次例行的退伍軍人桿菌檢查,尤其應選擇在冷卻空調系統開始使用前的時機,以便判斷消毒與清洗的需要性。
分析冷卻水塔水檢體溫度及pH值和嗜肺退伍軍人桿菌檢出率的關係,發現水溫介於25℃~30℃之間及pH值介於5.0~6.0之間檢出率為最高,分別為30.1%(35/126)和31.7%(39/123);至於冷卻水塔大小(噸位)和檢出率則沒有相關性。
從問卷調查發現冷卻水塔清洗次數越頻繁(每月一次)或使用漂白水進行消毒者,其嗜肺退伍軍人桿菌檢出率最低,分別為20.9%(5/24)及15.3%(17/111),但在冷卻水塔使用年限方面,則發現並沒有明顯的相關性。同時,問卷調查亦發現大樓管理人員或一般民眾願意其水塔進行一年二次的退伍軍人桿菌檢查和及其等對退伍軍人病及病原的認知上,均高達86.7%(209/241)和87.1%(210/241),可見台北市民普遍認知退伍軍人病並樂於進行水塔檢驗。
本研究利用簡便過濾法之操作流程偵測冷卻水塔中退伍軍人桿菌所獲得的高檢出率結果,可知其確為一種有效之檢測方法,由於現場採檢對公共場所之檢驗結果將較具有公信力,同時可免除檢體因運送而導致退伍軍人桿菌死亡或雜菌增生之困擾,且困檢驗之水檢體量由50ml增加為1,000~2,000ml而更可提升檢驗之準確性,又所使用的培養基費用較低而可降低檢驗成本,因此簡便過濾法為一種值得推廣之冷卻水塔中退伍軍人桿菌檢測方法。
From July 1997 to June 1998, we have used a simple portable charged water sampler, disposable filtration membrane apparatus and selective buffer charcoal yeast extract medium containing cephalothin, colistin, vancomycin, and cycloheximide (BCYEα agar w/CCVC) to survey the prevalence of Legionella pneumophila in cooling towers at 611 different locations in Taipei. Among 403 independent buildings, 145 are positive for L. pneumophila (35.0 %). Based on the character of the buildings, we found the prevalent rates of L. pneumophila in government office buildings, hospitals, private-owned buildings, schools, theaters, hotels, supermarkets or department stores, and KTV (MTV) are 38.9 % (63/162), 48.4 % (30/62), 25.0 % (19/76), 39.3 % (11/28), 25.6 (7/27), 13.3 % (2/15), 30.4 % (7/23), and 42.9 % (6/14) respectively. Regarding to the building types, the prevalent rate of hospital is the highest, and KTV (MTV) next Among 618 cooling towers, there are 169 towers positive for Legionella pneumophila. And the prevalent rate of L. pneumophila in cooling towers of the above building types are 30.4 % (72/237), 39.6 % (36/91), 16.4 % (23/140), 28.9 % (13/145), 24.2 % (8/33), 15.0 % (3/20), 21.1 % (8/38), and 40.0 % (6/15) respectively. The prevalent rate of L. pneumophila in cooling towers of KTV (MTV) is the highest, and hospital next.
We analyzed the Legionella spp. isolated from the cooling towers and found that 86.3 % (177/205) are L. pneumophila in which 59.3 % (105/177) are L. pneumophila serogroup 1. To find a method for the detection of Legionella from the environment can meet the need of hospital's Microbiology Laboratories, we compared the recovery rates of Legionella spp. from water samples known as positive for Legionella spp. by both filtration and centrifugation. When we examine the 50 ~ 500 ml volume of water samples, the numbers of total counts (Legionella spp. and non-Legionella flora) and Legionella spp. recovered by centrifugation method are higher than that of filtration. When examining the 1,000 ~ 2,000 ml volume of water samples by filtration, however, the numbers of total counts and Legionella spp. recovered is 9.7~23.3 folds and 7.8~22.2 folds respectively higher than centrifugation as examining only the volume 50 ml volume of water samples. In our study, we also found that all water specimens can be filtrated over the 200 ml, and of which 78.6 % (486/618) can be filtrated over 1,000 ml volume.
Because of the volume of water specimens filtrated is related to the level of cleansing of cooling tower. In our study, we find that when the volume of water specimens filtrated is 1,000~2,000 ml, the prevalent rate of L. pneumophila is 26.5 % (129/486). When the water volume filtrated is 500 ~ 1,000 ml, the prevalent rate is 29.2 % (24/82), and 200~500 ml volume, 33.3 % (16/48). This indicates that the prevalent rate of L. pneumophila in seldom cleaned-up, dirty cooling tower is higher.
We survey the prevalent rate of the cooling towers positive for L. pneumophila after cleaned up and disinfected, and found that the prevalent rate of buildings positive for L. pneumophila is 2.8 % (1/36), and of cooling towers, 4.1 % (2/49). We also monitor every three months or six months hereafter on the prevalent rate of cooling towers negative for L. pneumophila and found that only one cooling tower of the specific designated buildings is positive ( 6.7 %, 1/15), and for those randomly selected building 6.4 % (6/94). Therefore, we recommended that the cooling towers should be routinely examined for L. pneumophila each six months, especially at the time starting to operate the cooling water system.
We analyzed the relation between the temperature and pH of water specimen and the prevalent rate of L. pneumophila and found that the prevalent rates of specimen's temperature between 25℃~30℃ and pH between 5.0~6.0 are the highest, 30.1 % (35/126) and 31.7 % (39/129) respectively. The sizes of cooling towers is nothing to do with the prevalent rate.
To analyze the feedback of questionnaires, we found that the more frequently cleaned-up and had disinfected by chlorination, the lower the prevalent rate of L. pneumophila in cooling towers. The age of cooling towers, however, is not related to the prevalent rate. We also found that there are 86.7 % (209/241) of the managing person in the buildings are willing to accept the examination of L. pneumophila from cooling towers twice a year, and 87.1 % (210/241) of them have enough knowledge on the etiology of Legionnaire disease.
In conclusion, we have successfully designed a simplified method for the detection of L. pneumophila from cooling towers. The procedures (i) allowed field-collect specimens, (ii) can obtain accurate results which could be more trusted by public, especially for the popular locales, and (iii) will not cause death of Legionella spp. or growth of contaminated flora during specimen's transportation. The volume of specimens applied to the method is increased from 50 ml to 1,000~2,000 ml, so the result of test will be more precised. The cost of the media used in the method is relatively lower than that of others, and the total cost of laboratory expense will be decreased. Therefore, the simplified filtration method will be of worthy to recommend when survey Legionella spp. from the cooling towers enforced.
None

所屬典藏

測試學系
顯示完整詮釋資料 統計資料

引用此條目

張政雄 (1999). 比較以簡易濾膜法及傳統方法偵測空調冷卻水塔中退伍軍人桿菌盛行率之有效性-+-Legionella pneumophila from cooling tower in Taipei: Prevalence, Epidemioiogical Analysis, and Comparison of the effectiveness of Detteetion Methods and Disinfectants. https://thesis.lib.nycu.edu.tw/handle/20.500.14371/17015