液冷板應用於 1U 伺服器單相浸泡式冷卻之實驗研究
Experimental study on the liquid-cooled cold-plate for 1U server single-phase immersion cooling
摘要
In this study, the thermal performance of a single-phase immersion cooling system for a 1U server was investigated using a liquid-cooled cold-plate as the heatsink. Two different working fluids, Noah3000A and PAO-4 were tested, and their results were compared with those of air-cooled heatsink. The study also explored variations in whether the cold-plate was immersed in the liquid, the design of the cold-plate, and the design of fin in the cold-plate. Comparing the test results of the cold-plate with air-cooled heatsink, it was found that the system performance of the air-cooled heatsink varied with changes in fluid viscosity, with better results observed when using a low-viscosity dielectric liquid. However, in the case of the cold-plate system, the improvement in fluid bypass effect and the higher specific heat and thermal conductivity of PAO-4 resulted in better performance when using PAO-4 under small flowrate. Furthermore, the importance of improving the fluid bypass effect was evident from the trend of system thermal resistance varying with flowrate. When the flowrate increased from 1 Lpm to 3 Lpm, the system thermal resistance decreased by 39.7% when using the cold-plate with Noah3000A, whereas using the air-cooled heat sink only resulted in a 9.7% decrease, showing a significant difference. The test results of whether the liquid-cooled cold-plate was immersed in the liquid showed that immersing the cold-plate in the liquid effectively utilized the heat transfer area of the cold-plate. The enclosed cold-plate with immersion performed better in both working fluid. At a flowrate of 1 Lpm, the thermal resistance decreased by 7.2% for Noah3000A and 9.4% for PAO-4. When the flow rate increased to 3 Lpm, the performance difference between immersed and non-immersed was smaller due to the significant difference in thermal resistance between the inside and outside of the cold-plate. The thermal resistance decreased by 2.7% for Noah3000A and 3.9% for PAO-4. The test results of variations in cold-plate design indicated that in the system with Noah3000A, the dual-open cold plate performed better due to the impingement cooling effect. However, in the system with PAO-4, the impingement cooling effect was weaken by high fluid viscosity. Therefore, the enclosed cold-plate showed better result.The study of variations in cold-plate fin design showed that in both working fluid, the heat transfer capacity of the system effectively improved with reducing the fin pitch.
本研究在 1U 伺服器規格下的單相浸泡式冷卻(Single-phase immersion cooling)系統中,使用液冷板(Liquid-cooled cold-plate)作為散熱器進行熱傳性能研究,並在兩種不同的工作流體介電液Noah3000A、介電油 PAO-4 中進行測試,將其測試結果與空冷散熱器做比較,同時變化冷板有無浸泡在液體、冷板的設計與冷板內部鰭片的設計,做一完整的探討。在冷板與空冷散熱器的測試結果比較中,結果說明空冷散熱器的系統性能主要由流體黏度決定,使用低黏度的介電液測試結果較佳。但在使用冷板的系統中,因流體 Bypass 效應改善,且 PAO-4 的比熱、熱傳導係數均較 Noah3000A 大,因此低流量下,使用 PAO-4 的測試結果反而較佳。從系統熱阻隨流量變化的趨勢也可以了解改善流體Bypass 效應的重要性,當流量由 1 Lpm 上升至 3 Lpm 時,在Noah3000A 中使用冷板的系統熱阻下降了 39.7 %,而使用空冷散熱器只下降了 9.7 %,兩者有明顯的差異。於液冷板有無浸泡在液體的測試中,結果顯示將冷板浸泡在液體,能較有效善用到冷板的散熱面積,在兩種工作流體測試中,封閉式冷板有浸泡的性能皆較好,流量 1 Lpm 下,流體為 Noah3000A 時熱阻下降 7.2 %,流體為 PAO-4 時下降了 9.4 %,而當流量上升至 3 Lpm時,因冷板內外熱阻差異大,熱主要往冷板內部做傳遞,因此有無浸泡的性能差異較小,流體為Noah3000A 時下降 2.7 %,流體為 PAO-4 時,熱阻下降了 3.9 %。冷板設計變化的研究中,在流體為 Noah3000A 的系統內,使用雙開式冷板因衝擊冷卻(impingement cooling)效應的影響,性能最佳。但在流體 PAO-4 中,因流體黏度高、流動性差導致衝擊冷卻效應下降,因此使用封閉式冷板的性能反而較佳。冷板鰭片設計變化的研究結果顯示,因冷板改善了流體 Bypass效應,因此不管在介電液還是介電油的系統,系統熱傳能力皆隨著鰭片間距加密而有效地提升。