冷板在單相浸沒冷卻系統中強化熱傳的應用研究

Research on the Application of a Cold Plate in a Single-Phase Immersion Cooling System to Enhance Heat Transfer

檔案

全文將於 2029年7月1日 起公開。

日期

2024

類型

語言

中文

摘要

由於傳統浸沒冷卻系統結構對壓降分佈的影響,全部或大部分流體並沒有流經主熱源(如:中央處理器(CPU)),而是流向壓降更低的通道,將此現象稱之為旁通效應(Bypass)。旁通效應往往帶來較差的散熱表現,為消除旁通效應的影響,本文研究了在介質流體(Noah@3000A(簡稱:NO-3)和PAO-4)單相浸沒冷卻中採用冷板對傳統浸沒冷卻系統進行改進的方法。
本研究以實驗和CFD結合的方法,CPU熱功率為300 W,流率範圍從1到3 LPM,配置包括側開、全封閉和雙開設計,搭配長度為60 mm,寬度為48 mm,高度為3 mm,不同間距和厚度的鰭片。分別在介電液(NO-3)和介電油(PAO-4)中實驗測試了熱分佈和流場以及介質流體的性能差異。結果表明,浸沒冷板減少流體旁通效應效應,提高熱性能。與傳統系統相比,高黏度介電油作為冷卻劑可獲得顯著改善,在低流速和高流速下分別提高36.1%和41.6%。熱阻隨流率增大而減小,尤其對於NO-3。將冷板浸沒在液體中可以增強對流換熱,在低流速下NO-3和PAO-4的熱阻分別降低7.2%和9.4%。較小的鰭片間距通過消除旁路持續降低阻力。出口結構顯著影響熱阻,封閉冷板對PAO-4的表現最好,雙開冷板對NO-3的表現最好。PAO-4和NO-3之間熱傳行為的差異與層流和湍流特性以及衝擊效應有關。
為了進一步提升微通道冷板的性能,提出了上下層不等的新型結構。新型結構上層和下層不同的幾何結構,使得上層壓降明顯大於下層,逼迫低溫冷卻液更多的流向下層通道,從而獲得更好的整體熱性能。本文針對厚度在0.4 ~ 0.6 mm,間距在1.3 ~ 1.8 mm尺寸範圍為的鰭片,在體積流率為 3 LPM,CPU功率提升至500 W,幫浦功率1.26 W條件下,利用回應面法 (Response surface methodology,RSM)對鰭片上下層厚度和上下層通道寬度開展了優化。通過優化使得散熱性能進一步提升,比傳統單層和雙層微通道散熱鰭片熱阻分別降低9.42%和4.45%。在伺服器開展驗證,冷板浸沒系統採用PAO-4作為工作流體,與採用Pin Fin之浸沒冷區系統採用PAO-6作為工作流體相比,在體積流率3 LPM時,熱阻下降了59.99%,進一步提升了浸沒冷卻的整體性能,使得伺服器在較低的體積流率1 LPM時,也有著良好的表現,熱阻比原實驗最高流率4 LPM時下降了36.03%。
Due to the influence of the traditional immersion cooling system structure on the pressure drop distribution, all or most of the fluid does not flow through the main heat source (such as the CPU), but instead flows through the channel with a lower pressure drop, which is called the bypass effect. In order to eliminate the bypass effect, which often leads to poor heat dissipation, a method to improve the traditional immersion cooling system by using cold plate in single-phase immersion cooling of dielectric fluid (Noah@3000A(NO-3) and PAO-4) was studied.
In this study, the thermal power of the CPU is 300 W, the flow rate ranges from 1 to 3 LPM, and the configuration includes enclosed,side-open and double-open designs, with fin lengths of 60 mm, widths of 48 mm, heights of 3mm, different spacing and thickness. The thermal distribution and flow field of dielectric fluid (NO-3) and dielectric oil (PAO-4) were experimentally tested, and the properties of dielectric fluid were investigated. The results show that the combination of cold plate reduces the effect of fluid bypass effect and improves the thermal performance. The high viscosity dielectric oil can be significantly improved as a coolant compared to conventional systems,36.1% and 41.6% higher at low and high flow rates, respectively. Thermal resistance decreases with increasing flow rate, especially for NO-3. Immersion cold plates can enhance convective heat transfer and reduce the thermal resistance of NO-3 and PAO-4 by 7.2% and 9.4%, respectively, at low flow rates. The smaller fin spacing continuously reduces drag by eliminating bypass. The thermal resistance is significantly affected by the exit structure. The closed cold plate exhibited the best performance on PAO-4, and the double-open cold plate exhibited the best performance on NO-3. The difference of heat transfer behavior between PAO-4 and NO-3 is related to laminar and turbulent flow characteristics and impinging effect.
In order to further improve the performance of the micro-channel cold plate, a new structure with different upper and lower layers is proposed. The different geometry of the upper and lower layers of the new structure makes the upper pressure drop significantly greater than the lower layer, forcing more low-temperature coolant to flow to the lower channel, so as to obtain better overall thermal performance. In this paper, for fins with Thickness = 0.4 ~ 0.6 mm and Fin Pitch = 1.3 ~ 1.8 mm, the volume flow rate is 3 LPM, the CPU power is increased to 500 W, and the pump power is 1.26 W. Response surface methodology (RSM) was used to optimize the thickness of upper and lower layers of fins and the width of upper and lower channels. The heat dissipation performance is further improved through optimization, and the thermal resistance is reduced by 9.42% and 4.45%, respectively, compared with the traditional single-layer and double-layer micro-channel heat dissipation fins. It is verified in the Server that the cold plate immersion system uses PAO-4 as the working fluid. Compared with the Pin Fin immersion cooling system using PAO-6 as the working fluid, the thermal resistance decreases by 59.99% at the volume flow rate of 3 LPM, which further improves the overall performance of immersion. The Server also has a good performance at a low volume flow rate of 1 LPM, and the thermal resistance is reduced by 36.03% compared with the highest flow rate of 4 LPM in the original experiment.

所屬典藏

機械工程學系
顯示完整詮釋資料 統計資料

引用此條目

張永棟 (2024). 冷板在單相浸沒冷卻系統中強化熱傳的應用研究. https://thesis.lib.nycu.edu.tw/handle/20.500.14371/2133

BibTeX RIS

引用文字依 APA 第 7 版格式自動產生,使用前請再核對。

分享

永久網址:https://thesis.lib.nycu.edu.tw/handle/20.500.14371/2133