介電液FC-72在狹窄矩形空間的池沸騰研究
Study of Pool Boiling of Dielectric Fluid FC-72
摘要
摘要
本論文是以介電液FC-72為工作流體在一大氣壓下,狹窄矩形空間的池沸騰實驗。在狹窄矩形空間下方為面積10mm×10mm的銅片加熱面,上方為壓克力板,兩端以壓克力板檔住,可分別調整上下板的間隙S及加熱面與水平的夾角Θ,即S=0.5mm、1mm、2mm及3mm,以及Θ=0∘、45∘、90∘。實驗目的在比較間隙大小、加熱面角度在起始過熱度、核沸騰熱傳與臨界熱通量,並與開放式的池沸騰結果比較。實驗結果顯示Θ=0∘時,熱通量低於30kW/m2,S=1mm熱傳係數較開放式佳。水平加熱時,四種間隙的臨界熱通量都比開放式低很多。Θ=45∘與90∘時,小間隙(0.5mm)可以增強低熱通量時的熱傳係數,且S=2mm及S=3mm其臨界熱通量皆超越開放式。
本論文是以介電液FC-72為工作流體在一大氣壓下,狹窄矩形空間的池沸騰實驗。在狹窄矩形空間下方為面積10mm×10mm的銅片加熱面,上方為壓克力板,兩端以壓克力板檔住,可分別調整上下板的間隙S及加熱面與水平的夾角Θ,即S=0.5mm、1mm、2mm及3mm,以及Θ=0∘、45∘、90∘。實驗目的在比較間隙大小、加熱面角度在起始過熱度、核沸騰熱傳與臨界熱通量,並與開放式的池沸騰結果比較。實驗結果顯示Θ=0∘時,熱通量低於30kW/m2,S=1mm熱傳係數較開放式佳。水平加熱時,四種間隙的臨界熱通量都比開放式低很多。Θ=45∘與90∘時,小間隙(0.5mm)可以增強低熱通量時的熱傳係數,且S=2mm及S=3mm其臨界熱通量皆超越開放式。
ABSTRACT
The goal of this experiment is to study characteristic of pool boiling of dielectric fluid FC-72 in a narrow rectangular space under one atmosphere. The narrow rectangular space consists of a heated surface made of a smooth copper plate with 10 mm × 10 mm area and a parallel acrylic plate with two confined side edges .The gap size S and the inclination angle Ө between the heated surface and the horizon are S=0.5 mm, 1 mm, 2 mm and S=3 mm, and Ө=0°, 45°, 90° separately. The onset of boiling, nucleate heat transfer and critical heat transfer were studied . The results showed that for Ө=0°, under low heat flux 30 kw/m2 and S=1 mm the heat transfer coefficients of this experiment were found better than those of unconfined one. For Ө=0°, the critical heat fluxes for all gaps were depressed compared those of the unconfined one. For Ө=45° and Ө=90°, the smallest gap of 0.5 mm could enhance the heat transfer coefficients and if under low heat flux, especially for S=2 mm and 3 mm and the comes critical heat fluxes were found higher than these of the unconfined one.
The goal of this experiment is to study characteristic of pool boiling of dielectric fluid FC-72 in a narrow rectangular space under one atmosphere. The narrow rectangular space consists of a heated surface made of a smooth copper plate with 10 mm × 10 mm area and a parallel acrylic plate with two confined side edges .The gap size S and the inclination angle Ө between the heated surface and the horizon are S=0.5 mm, 1 mm, 2 mm and S=3 mm, and Ө=0°, 45°, 90° separately. The onset of boiling, nucleate heat transfer and critical heat transfer were studied . The results showed that for Ө=0°, under low heat flux 30 kw/m2 and S=1 mm the heat transfer coefficients of this experiment were found better than those of unconfined one. For Ө=0°, the critical heat fluxes for all gaps were depressed compared those of the unconfined one. For Ө=45° and Ө=90°, the smallest gap of 0.5 mm could enhance the heat transfer coefficients and if under low heat flux, especially for S=2 mm and 3 mm and the comes critical heat fluxes were found higher than these of the unconfined one.