dc.description.abstract |
由於一般小居室(面積 200m2),若堆積可燃物發熱量大,採用「建築物防火避難安全性能驗證技術手冊」進行居室避難安全性能驗證時,有其困難性。故本研究已發展一套適用小居室火災發生時煙層下降預測之簡易二層驗證技術。其數學模式係將空間分為上下兩層,再以質量和能量守衡方程式描述火場熱煙流動形式,透過輸入居室相關條件(如面積、高度、隔間牆材料和排煙方法)及火源大小,即可進行小居室煙流分析。該程式已經過火災模擬軟體FDS和前述驗證技術手冊之模擬結果以及相關實驗數據進行相互比較來驗證其可靠度,結果顯示該程式在適用範圍內,可以相當的能準確預估火場情境。 本研究在該簡易二層程式既有架構上,再予以精進。增加補氣口的設置,考慮由逃生門之排出之煙層質量,以更符合質量守恆之定義,減少煙層於質量流率上的計算誤差;此外亦另加入居室夾層之計算應用,以評估目前常見挑高空間含夾層之居室火災煙流危險度,同時借助FDS 數值模擬軟體進行相關驗證。 | |
dc.description.abstract |
If the fire load in a general small room, whose area 200m2, is large enough, then the evaluation of occupancy egress safety as a fire occurs by using the technical manual of building fire-evacuation performance evaluation is very hard to pass authority requirement. Therefore, this research team has been developed a simple two-zone model for smoke layer descending in a room fire. The model divides the room an upper hot layer from a lower cold layer. The mass and energy conservation equations are used to describe the smoke movement in the room fire. The input data include the area, height, partition wall materials and fire load. This predicted results by such model have been justified the corresponding ones obtained from the Fire Dynamics Simulator (FDS) and the technical manual mentioned previously. It also shows the fairly good agreements with the related measurements from the fire experiments. Those indicate that the simple two-zone model for smoke layer descending in a room fire can predict the fire behaviors very well in a suitable space. This study proposes to add air-inlet vent on this two-zone fire model.It considers the mass of smoke layer which exhaust through air-inlet vent into air to better meet the definition of mass conservation. It is also reduces the errors in the calculation of mass fluxes. In addition, the smoke movement in a room with a mezzanine is also taken into consideration in order to evaluate its hazardous degree if a fire occurs in this space. The corresponding simulations by using FDS are also carried out to justify the model. | |
dc.description.abstractopendate |
||
dc.description.degree |
碩士 | |
dc.description.tableofcontents |
摘要 IABSTRACT II致謝 IV目錄 V表目錄 IX圖目錄 X單位符號對照表 XII第一章 緒論 11.1研究動機與目的 11.2文獻回顧 41.3研究內容 10第二章 簡易二層法解說與推導 122.1簡易二層法源由 122.2火源設計 132.3火源成長率αf,αm 162.3.1堆積可燃物之火災成長率αf 172.3.2內部裝修材料之火災成長率αm 192.4煙生成率ms 192.5居室有效排煙率計算 212.5.1自然排煙計算 212.5.2機械排煙計算 222.5.3中性層與煙囪效應 222.6熱輻射 252.6.1熱輻射之計算 252.6.2形狀因子之計算 282.7牆壁熱損失率計算 292.8有效排煙熱損失計算 302.9煙層溫度計算 302.10煙層密度計算 302.11煙層厚度計算 312.12煙層高度計算 322.13簡易二層法解題程序 332.14C++撰寫 33第三章 模擬軟體介紹 353.1火災模擬軟體(FDS) 353.1.1流體力學之統御方程式 353.1.2差分方程式 393.1.3燃燒模式 423.1.4熱輻射之統御方程式 453.1.5邊界條件 473.2模型建立軟體PyroSim 50第四章 結果與討論 554.1前言 554.2簡易二層法適用範圍 554.3人員安全標準判斷 554.4本研究之簡易二層法版本歷程介紹 564.5增設自然補氣口與舊版簡易二層法之比較 604.5.1邊界條件設定 604.5.2模擬結果 614.6夾層情境計算結果 714.6.1情境設定介紹 714.6.2.邊界條件設定 734.6.3情境一模擬結果 734.6.4情境二模擬結果 754.6.5情境三模擬結果 764.6.6情境四模擬結果 784.7簡易二層法與檢證法、FDS於100m2至500m2之比較 814.7.1邊界條件設定 814.7.2模擬結果 82第五章 結論與建議 875.1結論與建議 875.2未來工作 89參考文獻 90 | |
dc.identifier.citation |
1.「建築技術規則」,內政部營建署,2005。2.「各類場所消防安全設備設計標準」,內政部消防署,2004。3.「建築物防火避難安全性能驗證技術手冊」,內政部建築研究所,2009。4.McGrattan K. B.,“Fire Dynamics Simulator Version 6-Technical Reference Guide Volume 1: Mathematical Model,” National Institute of Standard and Technology, USA, November, 2013.5.SIMULEX User Guide, IES, 1998.6.L. Meng, W.K. Chow, “Mathematical Analysis and Possible Application of the Two-Layer Zone Model Firm”, International Journal on Engineering Performance-Based Fire Codes, Vol.40, No 1, pp.13-22, 2002.7.Qidan Zhu, Qiuhong Zhu, Chengtao Cai, “Simulation of Vessel's Cabin Fire Based on Two-layer Zone Model”, Electronics, Communications and Control, pp.1669 – 1672, 2011.8.Keichi S, Kazunori H, Takeyoshi T, “A multi-layer zone model for predicting fire behavior in a single room,”Fire safety science, Proceedings of the seventh international symposium, 2003.9.Chen Xiaojun, Yang Lizhong, Deng Zhihua, Fan Weicheng, “A multi-layer zone model for predicting fire behavior in a fire room,” Fire Safety Journal, Vol.40, pp.267–281, 2005.10.Harada K, “Practical fire models used in building safety design,” International Workshop on Practical Application of Computing Fire Models, 2006.11.L. Yi, W.K. Chow, Y.Z. Li, R. Huo, “A simple two-layer zone model on mechanical exhaust in an atrium,” Building and Environment, Vol.40, pp.869-880, 2005.12.W.K. Chow, L. Yi, C.L. Shi, Y.Z. Li, R. Huo, “Mass flow rates across layer interface in a two-layer zone model in an atrium with mechanical exhaust system” Building and Environment, pp.1198-1202, 2006.13.R. Huo, W.K. Chow, X.H. Jin, Y.Z. Li, N.K. Fong, “Experimental studies on natural smoke filling in atrium due to a shop fire”Building and Environment, Vol.40, pp.1185-1193, 2005.14.Zukoski E.E, B.M. Cetege, T.Kubota, “ Entrainment and Flame Geometry of Fire Plumes.”NBS-GCR-82-402, 1982.15.NFPA 92B“Guide for Smoke Management Systems in Mall, Atria, and Large Areas”, National Fire Protection Association, 2000.16.L.H. Hu, Y.Z. Li, R. Huo, L. Yi, W.K.Chow, “Full-scale Experimental Studies on Mechanical Smoke Exhaust Efficiency in an Underground Corridor”, Building and Environment,pp.1622-1630, 2006.17.K.Y. Li, L.H. Hu, R. Huo, Y.Z. Li, Z.B. Chen, S.C. Li, X.Q. Sun, “A Mathematical Model on Interaction of Smoke Layer with Sprinkler Spray”, Fire Safety Journal, Vol.44, pp.96-105, 2009.18.Frederick W. Mowrer, James A. Milke and Jose L. Torero, “A Comparison of Driving Forces for Smoke Movement in Buildings”, Journal of Fire Protection Engineering, Vol.14, pp.237-264, 2004.19.Zhuman Fu, George Hadjisophocleous, “A two-zone "re growth and smoke movement model for multi-compartment buildings”, Fire Safety Journal, Vol.34,pp.257-285, 2000.20.Walter W. Jones, Glenn P. Forney, “Improvement in predicting smoke movement in compartmented structures”, Fire Safety Journal, Vol.21,pp.259-297, 1993.21.Xia Zhang, George Hadjisophocleous “An improved two-layer zone model applicable to both pre- and post-flashover fires”, Fire Safety Journal, Vol.53,pp.63-71, 2012.22.Petterson, N.M., Assessing the Feasibility of Reducing the Grid Resolution in FDS Field Modeling Fire Engineering Research Report (Master Thesis Supervised by Charley Fleischmaan),University of Canterbury, New Zealand, February 2002.23.王鵬智,「居室火災避難容許時間基準之驗證研究」,台灣科技大學建築系博士論文,200724.Shi B. K., “The Smoke Layer Descending Simulation in a Small Space by Using Two-Layer Zone Model”, 2012.25.Roger Harrison, “Smoke Control in Atrium Building-A Study of the Thermal Spill Plume”, Fire Engineering Research Report (Master Thesis Supervised by Michael Spearpoint) University of Canterbury, New Zealand, July 2004.26.Kumar S., “Air entrainment into balcony spill plumes”, Fire Safety Journal 45,pp.159-167,2010.27.Yu W. S, “ The Study of Two-Layer Zone Model for Space with Mezzanine”, 2013.28.W.K. Chow, Y. Gao, “Buoyancy and inertial force on oscillations of thermal-induced convective flow across a vent”, Building and Environment, Vol.46, pp.315-323, 2011.29.C. W. Wu, T. H. Lin, C. J. Chen, M. J. Tsai, “Smole leakage through wall opening s in a fire”, Experimental Thermal and Fluid Science 32,pp.29-37, 2007.30.X. Wang, R. Zhou, “Simulaton of a compartmentalized fire breaching its container under the impact of different heat release rates”, Journal of Harbin Engineering University, 2009.31.陳弘毅, 火災學, 1999.32.P. H. Thomas, C. Ian Smith, “A note on fully developed fires in large compartments”, Fire Safety Journal 35,pp.67-69, 2000.33.Heskestad, G. “Engineering relations for fire plumes”, Fire Safety Journal 7, pp.25-32,1984.34.Siegel R, Howell J, “Thermal radiation Heat Transfer(Third Edition) ”, 1983.35.Tanaka, Yamada. “BRI2002:Two Layer Smoke Transport Model Fire Science and Technology”, 2003. | |
dc.identifier.uri |
https://hdl.handle.net/20.500.14371/59778 | |
dc.language.iso |
中文 | |
dc.relation.alma |
990055205830206772 | |
dc.relation.page |
93 | |
dc.subject.keyword |
火災模擬軟體 | |
dc.subject.keyword |
簡易二層法 | |
dc.subject.keyword |
補氣口 | |
dc.subject.keyword |
夾層 | |
dc.subject.keyword |
FDS(Fire dynamic simulator) | |
dc.subject.keyword |
Two-layer zone model | |
dc.subject.keyword |
Air-inlet vent | |
dc.subject.keyword |
Mezzanine | |