廠務設施警報系統設計合理性探討

A Study on Rationalization of Facility Alarm Systems

檔案

日期

2019

類型

語言

中文

摘要

太陽能電池製造業所建置的廠務設施都依據各設施自行設置系統並監測運轉狀態,因系統特性不同各自設定相對應警報種類與警報範圍,主要讓監測人員可以藉由各項警報的觸發,提醒應採取的預先應變措施,以求即時紓解異常運作狀態,避免人員傷亡,並將可能造成工廠的影響降到最低。
本研究將彙整廠務設施系統警報歷史資料,進行歸類與分級,根據ANSI/ISA18.2指引確認警報設定範圍所引起的警報觸發率,逐一瞭解警報設定的合理性,協助監測操作人員可以專注於高風險異常狀態的處理。
由於廠務設施系統種類多,本研究僅針對會對人員造成立即危害的系統進行討論,因此選定氣體供應及化學品供應兩大系統,利用研究方法彙整說明相關結論與建議,以期修正警報設定,確實達到系統運作偏離示警作用,讓作業人員可提早因應或採取必要的應變措施,降低中控室人員需進行判斷的次數與錯誤判斷機會,避免衍生可能的意外事故發生。
本研究與ANSI/ISA 18.2的要求或是建議的績效目標值進行比對,在ANSI/ISA 18.2警報管理生命週期的建議與實際的運轉情形,廠務設施系統的警報設計要求仍有一半未符合要求。從警報數量的觸發情形與ANSI/ISA 18.2建議的平均觸發量,大約有81%~87%左右的時間都在監控操作人員的可管理範圍。因此確認廠務設施的化學品與氣體供應系統的警報設定的合理性是可符合ANSI/ISA 18.2,但仍應該持續改善利用適時調整來優化警報系統並減少監控人員的工作負荷。
In solar cell manufacturing industry, the factory facilities are built up and monitored independently by system. The corresponding alarm types and alarm ranges are set by their unique system characteristics, which mainly allow personnel in charge of monitoring to respond to various alarms. Corrective measures must be taken to immediately resolve abnormal operating conditions to avoid harm to people, and to minimize the impact to the plant.
This study will collect the alarm history data from the facilities to classify and rank the alarms based on ANSI/ISA 18.2 guidelines. Furthermore the relationship between alarm trigger rate and alarm setting is used to analyze rationality of the alarm settings one by one to assist the operators responsible for monitoring. This will assist them to focus on handling of high-risk abnormal conditions.
Due to the variety of factory facilities system, this study focus on discusses those systems having immediately harmful effects to people. Therefore, the gas supply and chemical supply systems are selected. Relevant conclusions and recommendations are proposed using the research methodologies to validate the alarm settings. If the warning functions on operating condition deviations can be achieved, the Central Control Room operators can respond to the abnormal operating conditions more effectively to prevent possible accidents.
This study is aligned with the requirements of ANSI/ISA 18.2 or the recommended performance target values. In the ANSI/ISA 18.2 alarm management lifecycle recommendations and actual operational scenarios, the alarm design requirements for the facility system are still not consistent with half. From the triggering situation of the number of alarms to the average trigger amount recommended by ANSI/ISA 18.2, approximately 81%~87% of the time is within the manageable range of the monitoring operator. Therefore, it is reasonable to confirm that the alarm settings of the chemical and gas supply systems of the facility are meet the ANSI/ISA 18.2, but these systems should improvement continuously to optimize the alarm system and reduce the workload of the monitoring personnel.