摘要

有鑒於精密製程的生產環境要求與人員舒適性之考量,因此運轉過程中會產生振動而影響振動品質者,例如:冰水主機、泵浦等…應加裝避振器以隔離振動的傳遞。因業界沒有明確減振規範,設備商通常提供減振墊做為出廠基本配件,使用單位須自行選用適當避振器,或依廠房既有避振器的配置以其滿足環境振動之要求。

  本研究以冰水主機為標的,業界多以落地型彈簧避振器為主流,但業界時常將「避振器」寫作「避震器」令使用者產生混淆,以為「避振器」亦兼具抗震(地震)之功用。落地型彈簧避振器的主要承載方向為垂直向(以樓板之平面法線方向為基準),其橫向(Transverse direction)對於水平地震力沒有足夠的承載力,因此避振器並不具備抗震能力,臺灣南部科學園區的科技廠房在206地震(2016)中充分印證此事實,403地震(2024)亦有多起案例再次予以證實。業界在206地震後開發「摯震器」,以防止冰水主機於地震時因側向位移過大導致設備與彈簧避震器受損的可能性,惟不當的「摯震器」安裝方式會讓振動傳遞至樓板,而違背安裝彈簧避振器的初衷。實際上,為避免「摯震器」將冰水主機的振動能量傳遞到樓板,「摯震器」與機台間須留有間隙,當水平地震力導致冰水主機側移接觸到「摯震器」的狀態下才被動產生反制力,然而工程實務上多未意識到此細節。此外,設備商多將「摯震器」裝設於設備單一方向而忽略其正交方向,而功虧一簣。

  由於無法取得冰水主機設備進行整體結構(含避振器、摯震器)的減振與耐震實驗,本研究將結合試驗與數值模擬分析進行探討,透過單元件試驗方式找出落地彈簧的垂直與水平勁度,並將實驗所得參數用於數值模型中,由學理上證明其在冰機工作頻寬範圍內具減振功能,並評估冰水主機與減振彈簧在設計地震條件下之側位移量,計算對應之最大水平力作為摯震器的設計依據,同時完成冰水主機之地震歷時反應分析作進一步確認。
Given the stringent requirements of precision manufacturing environments and the consideration of personnel comfort, vibrations generated during operation—such as those from chillers and pumps—must be managed to ensure vibration isolation performance. To achieve this, vibration isolators should be installed to isolate vibration transmission. However, due to the lack of explicit industry standards for vibration control, equipment manufacturers typically provide vibration isolation pads as basic accessories. End-users are therefore required to independently select suitable vibration isolators or adapt them to existing isolation configurations to meet environmental vibration criteria.

This study focuses on chillers, where the use of floor-mounted spring vibration isolators is prevalent in the industry. However, confusion often arises because the term "vibration isolator" is frequently misinterpreted as "shock absorber," leading users to mistakenly assume that vibration isolators also provide seismic resistance. In reality, floor-mounted spring isolators are primarily designed to support vertical loads (perpendicular to the floor plane) and lack sufficient stiffness to resist horizontal seismic forces. This limitation became evident during the 206 earthquake (2016) in the Southern Taiwan Science Park and was further confirmed by multiple incidents during the 403 earthquake (2024).Following the 2016 earthquake, the industry developed "seismic restraints" (shock dampers) to prevent excessive lateral displacement of chillers during earthquakes, which could damage both the equipment and the spring isolators. However, improper installation of seismic restraints can inadvertently transmit vibrations to the floor, counteracting the purpose of the spring isolators. To address this issue, a gap must be maintained between the seismic restraint and the chiller, ensuring that the restraint only engages when lateral seismic forces cause the chiller to shift and contact the restraint. Unfortunately, this critical design consideration is often overlooked in engineering practice. Additionally, many manufacturers install seismic restraints in a single direction while neglecting orthogonal directions, thus compromising overall performance.

Due to the challenges of conducting full-scale vibration and seismic tests on chiller systems, this study adopts a combination of experimental and numerical simulation approaches. Unit tests are performed to determine the vertical and horizontal stiffness of floor-mounted spring isolators. These parameters are integrated into numerical models to theoretically validate their vibration isolation performance across the chiller’s operational frequency range. The study further evaluates the lateral displacement of the chiller and vibration isolators under design seismic conditions, calculates the corresponding maximum horizontal forces as a basis for seismic restraint design, and conducts time-history seismic response analysis to verify the overall dynamic performance of the chiller system.
顯示完整詮釋資料 統計資料

引用此條目

陳宜嫺 (2025). 冰水主機之減振與防震研究. https://thesis.lib.nycu.edu.tw/handle/20.500.14371/84580

BibTeX RIS

引用文字依 APA 第 7 版格式自動產生,使用前請再核對。