平滑管於冷凍油-冷媒混合物中池沸騰的通用關聯式研究
A Universal Correlation for Nucleate Pool Boiling for Smooth Tubes Subject to Lubricant-Refrigerant Mixtures.
摘要
本論文針對低全球暖化潛勢(Low-GWP)冷媒於光滑及強化管表面之核沸騰熱傳特性進行了全面性研究。研究重點為評估共沸型與低壓冷媒(特別是 R513A 與 R1233zd(E))與傳統冷媒(如 R134a 與 R245fa)之性能差異。核池沸騰實驗係於光滑銅管上進行,涵蓋廣泛的熱通量範圍(5–90 kW/m²)與飽和溫度區間(0–26.7 °C),並分別於有無添加聚酯類(POE)潤滑油的條件下進行比較。
實驗結果顯示,R513A 在整體熱傳係數(HTC)表現上穩定優於 R134a,提升幅度介於 20–25% 之間,特別是在較高飽和溫度條件下更為明顯。本研究亦對多項經驗公式進行驗證與比較,包括 Cooper、Ribatski 與 Jabardo、Jung、Stephan 與 Abdelsalam,以及 Kutateladze 等相關模型。其中,以 Ribatski 與 Jabardo 所提出之關聯式與實驗數據最為吻合,對 R513A 性能預估誤差僅約 5–10%。
就 R1233zd(E) 而言,當加入高黏度 POE 潤滑油 POEC-220(黏度 220 cSt)後,當潤滑油質量濃度超過 3% 時,熱傳係數呈現逐漸劣化現象,於油濃度達 10% 時,最大降幅高達 42.87%。然而,在中等壓力條件下(150–700 kPa),若油濃度低於或等於 3%,則可觀察到熱傳效能有所提升。
根據上述實驗結果,本研究進一步發展出一套適用於光滑管表面之冷媒-潤滑油混合物核池沸騰增強比的普適無因次關聯式。該模型整合了油質量濃度、約化壓力與溫度、分子量比、黏度、表面張力與無因次熱通量等關鍵參數。此關聯式經由含括多種冷媒(R-134a、R-507、R-1233zd(E)、R-1234ze(E)、R-454B)與潤滑油(POE、PVE 及其不同黏度變化)之 1,390 筆實驗數據進行驗證,成功捕捉增強與抑制兩種傳熱機制。該模型預測結果之平均絕對偏差為 0.117,平均絕對百分比誤差(MAPE)為 12.67%,決定係數 R² 則為 0.621。
本研究成果提供了重要之實驗觀察與預測工具,對於採用環境友善工質之高效節能冷凍空調系統設計具有實質參考價值。
實驗結果顯示,R513A 在整體熱傳係數(HTC)表現上穩定優於 R134a,提升幅度介於 20–25% 之間,特別是在較高飽和溫度條件下更為明顯。本研究亦對多項經驗公式進行驗證與比較,包括 Cooper、Ribatski 與 Jabardo、Jung、Stephan 與 Abdelsalam,以及 Kutateladze 等相關模型。其中,以 Ribatski 與 Jabardo 所提出之關聯式與實驗數據最為吻合,對 R513A 性能預估誤差僅約 5–10%。
就 R1233zd(E) 而言,當加入高黏度 POE 潤滑油 POEC-220(黏度 220 cSt)後,當潤滑油質量濃度超過 3% 時,熱傳係數呈現逐漸劣化現象,於油濃度達 10% 時,最大降幅高達 42.87%。然而,在中等壓力條件下(150–700 kPa),若油濃度低於或等於 3%,則可觀察到熱傳效能有所提升。
根據上述實驗結果,本研究進一步發展出一套適用於光滑管表面之冷媒-潤滑油混合物核池沸騰增強比的普適無因次關聯式。該模型整合了油質量濃度、約化壓力與溫度、分子量比、黏度、表面張力與無因次熱通量等關鍵參數。此關聯式經由含括多種冷媒(R-134a、R-507、R-1233zd(E)、R-1234ze(E)、R-454B)與潤滑油(POE、PVE 及其不同黏度變化)之 1,390 筆實驗數據進行驗證,成功捕捉增強與抑制兩種傳熱機制。該模型預測結果之平均絕對偏差為 0.117,平均絕對百分比誤差(MAPE)為 12.67%,決定係數 R² 則為 0.621。
本研究成果提供了重要之實驗觀察與預測工具,對於採用環境友善工質之高效節能冷凍空調系統設計具有實質參考價值。
This dissertation presents a comprehensive investigation into the nucleate pool boiling heat transfer characteristics of low-global-warming-potential (low-GWP) refrigerants on smooth and enhanced tube surfaces. The primary focus is on evaluating the performance of azeotropic and low-pressure refrigerants (specifically R513A and R1233zd(E)) in comparison with conventional refrigerants such as R134a and R245fa. Pool boiling experiments were conducted on smooth copper tubes across a wide range of heat fluxes (5–90 kW/m²) and saturation temperatures (0–26.7 °C), with and without the presence of polyolester (POE) lubricant oils.
Experimental results reveal that R513A consistently outperforms R134a in terms of heat transfer coefficient (HTC), with enhancements ranging between 20–25%, particularly at higher saturation temperatures. Several empirical correlations were evaluated against the experimental data, including those by Cooper, Ribatski and Jabardo, Jung, Stephan and Abdelsalam, and Kutateladze. Among these, the Ribatski and Jabardo correlation exhibited the closest agreement with experimental values, underestimating R513A’s performance by only 5–10%. For R1233zd(E), the introduction of high-viscosity POE lubricant POEC-220 (220 cSt) led to progressive degradation of heat transfer coefficient at oil mass concentrations beyond 3%, with reductions reaching up to 42.87% at 10% oil concentration. Enhancement, however, was observed at lower concentrations (≤3%) under moderate pressures (150–700 kPa).
Building on the experimental findings, a universal dimensionless correlation is developed to predict the enhancement ratio of nucleate pool boiling in refrigerant-lubricant mixtures for smooth tubes. The correlation integrates key parameters such as oil mass concentration, reduced pressure and temperature, molecular weight ratio, viscosity, surface tension, and dimensionless heat flux. Validation against an extensive dataset comprising 1,390 data points, including a variety of refrigerants (R-134a, R-507, R-1233zd(E), R-1234ze(E), R-454B) and lubricant oils (POE, PVE, and their viscosity variants), demonstrates the correlation’s ability to accurately capture both enhancement and suppression regimes. The proposed model achieves a mean absolute deviation of 0.117, a mean absolute percentage error (MAPE) of 12.67%, and an R² value of 0.621.
The outcomes of this research offer both experimental insights and a predictive framework essential for the optimized design of energy-efficient refrigeration and air-conditioning systems using environmentally sustainable working fluids.
Experimental results reveal that R513A consistently outperforms R134a in terms of heat transfer coefficient (HTC), with enhancements ranging between 20–25%, particularly at higher saturation temperatures. Several empirical correlations were evaluated against the experimental data, including those by Cooper, Ribatski and Jabardo, Jung, Stephan and Abdelsalam, and Kutateladze. Among these, the Ribatski and Jabardo correlation exhibited the closest agreement with experimental values, underestimating R513A’s performance by only 5–10%. For R1233zd(E), the introduction of high-viscosity POE lubricant POEC-220 (220 cSt) led to progressive degradation of heat transfer coefficient at oil mass concentrations beyond 3%, with reductions reaching up to 42.87% at 10% oil concentration. Enhancement, however, was observed at lower concentrations (≤3%) under moderate pressures (150–700 kPa).
Building on the experimental findings, a universal dimensionless correlation is developed to predict the enhancement ratio of nucleate pool boiling in refrigerant-lubricant mixtures for smooth tubes. The correlation integrates key parameters such as oil mass concentration, reduced pressure and temperature, molecular weight ratio, viscosity, surface tension, and dimensionless heat flux. Validation against an extensive dataset comprising 1,390 data points, including a variety of refrigerants (R-134a, R-507, R-1233zd(E), R-1234ze(E), R-454B) and lubricant oils (POE, PVE, and their viscosity variants), demonstrates the correlation’s ability to accurately capture both enhancement and suppression regimes. The proposed model achieves a mean absolute deviation of 0.117, a mean absolute percentage error (MAPE) of 12.67%, and an R² value of 0.621.
The outcomes of this research offer both experimental insights and a predictive framework essential for the optimized design of energy-efficient refrigeration and air-conditioning systems using environmentally sustainable working fluids.