公共危險物品工廠緊急避難之研究-以某生技廠為例
Emergency Evacuation Strategies for Facilities Handling Publicly Hazardous Substances: A Case Study of a Biopharmaceutical Factory
摘要
生技製藥業因大量使用易燃及反應性化學品,火災風險顯著升高,尤以COVID-19後廠區高密度運作使避難規劃更形重要。本文針對國內中大型生技廠進行火災避難模擬與實地演練交叉驗證,評估弱勢族群、壅塞區及逃生動線對總疏散時間之影響,並據此提出數據支持之設計建議,以提升應變效能與人員安全。
研究首先採用初步危害分析(Preliminary Hazard Analysis, PHA)辨識廠區內潛在風險熱點,後透過Pathfinder模擬建構全區模型,設計14種火災情境,其中包含不同樓層起火點、逃生路徑選擇、避難弱勢族群參與等變因,並整合自衛消防編組實際應變流程納入模擬機制,提升行為擬真性。
本研究在人流壅塞與路徑分析方面,A梯於模擬第31秒即進入高密度狀態4.2人/m²,平均滯留時間為12.6秒,與實地演練所觀察回堵點一致,驗證模擬在設計上具可用性;反觀B梯與碼頭區動線則有效分散壓力,若優先引導避難弱勢人員至非主流動線,整體避難完成時間可縮短超過51%。在設計情境4.1與4.2中,模擬第一位完成避難人員用時8.1秒,而熟悉碼頭動線之工程人員則平均避難時間不到78秒,顯示動線熟悉度與教育訓練為提升反應效率之關鍵要素。
本研究在實際演練與模擬結果分析比較後發現,情境4.1全員完成避難之最慢總完成時間為178.3秒,實地演練為329秒,誤差率為45.8%,經探討後發現,Pathfinder 模擬參數設定皆使用非無塵室區域步行速度,而生技廠房特性大多為居室中還有居室,較多不確定因素,這些因素確實延遲避難逃生時間,因此建議未來在執行Pathfinder 模擬時,需先考量是否有無塵室以及是否有較多居中居室等,若有則須在另外探討。在輪椅與拐杖使用者在模擬與演練中所需避難時間分別為176秒與177.2秒,之間誤差0.68%,顯示弱勢群體參數設定具可行性。此外Pathfinder模擬中加入門控開啟延遲設定,開門阻礙平均耗時約1.7秒/道門,總體平均對模擬完成時間增加9秒,證實門控反應為影響逃生效率的潛在關鍵因素之一。
研究首先採用初步危害分析(Preliminary Hazard Analysis, PHA)辨識廠區內潛在風險熱點,後透過Pathfinder模擬建構全區模型,設計14種火災情境,其中包含不同樓層起火點、逃生路徑選擇、避難弱勢族群參與等變因,並整合自衛消防編組實際應變流程納入模擬機制,提升行為擬真性。
本研究在人流壅塞與路徑分析方面,A梯於模擬第31秒即進入高密度狀態4.2人/m²,平均滯留時間為12.6秒,與實地演練所觀察回堵點一致,驗證模擬在設計上具可用性;反觀B梯與碼頭區動線則有效分散壓力,若優先引導避難弱勢人員至非主流動線,整體避難完成時間可縮短超過51%。在設計情境4.1與4.2中,模擬第一位完成避難人員用時8.1秒,而熟悉碼頭動線之工程人員則平均避難時間不到78秒,顯示動線熟悉度與教育訓練為提升反應效率之關鍵要素。
本研究在實際演練與模擬結果分析比較後發現,情境4.1全員完成避難之最慢總完成時間為178.3秒,實地演練為329秒,誤差率為45.8%,經探討後發現,Pathfinder 模擬參數設定皆使用非無塵室區域步行速度,而生技廠房特性大多為居室中還有居室,較多不確定因素,這些因素確實延遲避難逃生時間,因此建議未來在執行Pathfinder 模擬時,需先考量是否有無塵室以及是否有較多居中居室等,若有則須在另外探討。在輪椅與拐杖使用者在模擬與演練中所需避難時間分別為176秒與177.2秒,之間誤差0.68%,顯示弱勢群體參數設定具可行性。此外Pathfinder模擬中加入門控開啟延遲設定,開門阻礙平均耗時約1.7秒/道門,總體平均對模擬完成時間增加9秒,證實門控反應為影響逃生效率的潛在關鍵因素之一。
The biopharmaceutical industry extensively handles flammable, corrosive, and reactive chemicals, substantially elevating fire risks within its operational environments. Post-COVID-19 facility adaptations—characterized by increased production density and complex architectural zoning such as cleanrooms and nested compartments—have intensified the urgency of well-calibrated emergency evacuation planning. This study assesses evacuation effectiveness in a mid-to-large-scale Taiwanese biopharmaceutical plant through an integrated methodology combining Preliminary Hazard Analysis (PHA), Pathfinder agent-based simulations, and full-scale evacuation drills for cross-validation.
A total of 14 fire scenarios were developed based on variable ignition sources (e.g., first-floor warehouse, eighth-floor boiler room), escape route configurations, and human factors including vulnerable groups such as wheelchair and cane users. Simulations adopted a maximum occupant density of 4.2 persons/m², with walking speeds set at 1.19 m/s for general occupants and 0.6 m/s for vulnerable individuals. Door operation delays were also parameterized, averaging 1.7 seconds per door, to reflect access impedance.
Findings revealed that Staircase A reached high congestion levels within 31 seconds, resulting in average queuing delays of 12.6 seconds—closely matching congestion points recorded in actual drills. In contrast, Staircase B and the dock area demonstrated effective dispersal of occupant flow. Redirecting vulnerable individuals to these alternative routes led to a reduction in total evacuation time exceeding 51%. In Scenario 4.1, simulated total evacuation time was 178.3 seconds, compared to 329 seconds in drills—a deviation of 45.8%—largely due to the exclusion of cleanroom zoning and complex spatial structures in simulation parameters. The evacuation time for wheelchair and cane users differed by only 0.68% between simulation and real-world drills, validating the accuracy of assigned behavioral parameters. Incorporating door delay further increased the total evacuation time by approximately 9 seconds, indicating that door access latency is a non-negligible influence on evacuation performance.
This study confirms the feasibility and reliability of calibrated evacuation simulations in high-risk pharmaceutical environments and provides data-driven recommendations for enhancing emergency preparedness, occupant safety, and evacuation route design in cleanroom-intensive facilities.
A total of 14 fire scenarios were developed based on variable ignition sources (e.g., first-floor warehouse, eighth-floor boiler room), escape route configurations, and human factors including vulnerable groups such as wheelchair and cane users. Simulations adopted a maximum occupant density of 4.2 persons/m², with walking speeds set at 1.19 m/s for general occupants and 0.6 m/s for vulnerable individuals. Door operation delays were also parameterized, averaging 1.7 seconds per door, to reflect access impedance.
Findings revealed that Staircase A reached high congestion levels within 31 seconds, resulting in average queuing delays of 12.6 seconds—closely matching congestion points recorded in actual drills. In contrast, Staircase B and the dock area demonstrated effective dispersal of occupant flow. Redirecting vulnerable individuals to these alternative routes led to a reduction in total evacuation time exceeding 51%. In Scenario 4.1, simulated total evacuation time was 178.3 seconds, compared to 329 seconds in drills—a deviation of 45.8%—largely due to the exclusion of cleanroom zoning and complex spatial structures in simulation parameters. The evacuation time for wheelchair and cane users differed by only 0.68% between simulation and real-world drills, validating the accuracy of assigned behavioral parameters. Incorporating door delay further increased the total evacuation time by approximately 9 seconds, indicating that door access latency is a non-negligible influence on evacuation performance.
This study confirms the feasibility and reliability of calibrated evacuation simulations in high-risk pharmaceutical environments and provides data-driven recommendations for enhancing emergency preparedness, occupant safety, and evacuation route design in cleanroom-intensive facilities.