本研究以國立陽明交通大學教學館舍為例,探討以空間用途與設備特性為基礎之建築能源使用強度(EUI)預測架構。研究首先建立基本模型,以FICM空間用途比例、月均溫與工作日為迴歸自變數,初步掌握各館舍之用電趨勢;接著引入用途別用電密度與空間面積估算空間用電密度占比參數,試圖進一步反映負載差異;最終提出「研究修正參數模型」,針對研究用途進行動態權重調整,以補償實驗室空間設備異質性與使用行為差異所造成之預測誤差。
模型驗證結果顯示,光復校區導入研究修正參數後,分群館舍之R²皆超過0.99,MAPE低於2.5%,大幅優於前兩階段模型;跨年度應用中誤差皆控制於7%內,顯示時間延展性良好;最後整合光復與陽明校區之跨校區測試亦維持高擬合度,展現「研究修正參數模型」對不同建築類型之通用性。
整體而言,「研究修正參數模型」為本研究最具代表性的成果,適用於高等教育建築群之用電預測、節能管理與決策支援。研究結果顯示,透過分群建模與用途修正參數的設計,能有效提升校園建築能耗預測的準確度與應用彈性。未來此模型可作為校方推動節能政策與監測策略之依據,亦可提供其他高等教育建築群進行能效管理之參考。
This study proposes a predictive framework for estimating the Energy Use Intensity (EUI) of academic buildings, using National Yang Ming Chiao Tung University as a case study. The framework incorporates spatial function composition and equipment characteristics, aiming to address the limitations of traditional area-based indicators that overlook space-specific energy behaviors.
A three-stage multiple linear regression approach was developed. The baseline model utilizes FICM-defined space use proportions, monthly average temperature, and workdays as explanatory variables. Subsequently, power density estimates were introduced to derive weighted spatial electricity use ratios. To further improve accuracy, a “research adjustment coefficient model” was proposed to dynamically calibrate the weight of research space, capturing the heterogeneity of laboratory equipment and operational intensity.
The “research adjustment coefficient model” showed strong performance in validation, with R² values exceeding 0.99 and MAPE below 2.5%. It demonstrated robust temporal and cross-campus applicability, offering a reliable tool for energy prediction and performance management in higher education facilities. It provides useful implications for energy conservation strategies and data-driven campus sustainability planning.

所屬典藏