放射狀微流道衝擊式混合冷板使用介電液相變化之熱傳性能實驗研究
Experimental Investigation on Phase Change Heat Transfer Performance of a Radial Microchannel Jet Impingement Hybrid Cold Plate Using Dielectric Fluid
摘要
隨著運算元件發熱密度攀升,局部熱點問題日益嚴重,傳統單相液冷已難以因應,藉介電液相變化散熱提升散熱極限已成必然趨勢。然現行兩相微流道冷板於高熱通量下常因汽泡迅速膨脹引發逆流與局部燒乾,致壓降驟增、性能劣化。放射狀衝擊式冷板雖可抑制此現象,惟受加工精度限制,鰭片間距多僅達1 mm,且多以水或冷媒測試,缺乏介電液實驗數據。
本研究以金屬積層製造製作三款銅製放射狀微流道衝擊式混合冷板,最小鰭片間距達0.4 mm,並以HFE-7000、FC18P兩種介電液測試。結果顯示最佳冷板於0.95 LPM、293.15 K條件下,使用HFE-7000於74.3 W/cm²達最低熱阻0.0231 K/W,於接面溫度379.75 K下達最大熱通量90.8 W/cm²。HFE-7000因飽和溫度較低,同條件下熱阻較FC18P低14%;FC18P則因密度較高具較佳單相熱傳能力,可作為受REACH法規限制下之潛在替代方案。
本研究冷板即便採用沸騰更劇烈之介電液,仍優於文獻水冷之接面溫度控制,且較其他HFE-7000平行式或陣列式冷板於熱阻抗與幫浦負載權衡上具優勢,佐證放射狀流道於微小鰭片間距下仍能抑制兩相流不穩定性,可為次世代高熱密度電子元件散熱設計提供參考。
本研究以金屬積層製造製作三款銅製放射狀微流道衝擊式混合冷板,最小鰭片間距達0.4 mm,並以HFE-7000、FC18P兩種介電液測試。結果顯示最佳冷板於0.95 LPM、293.15 K條件下,使用HFE-7000於74.3 W/cm²達最低熱阻0.0231 K/W,於接面溫度379.75 K下達最大熱通量90.8 W/cm²。HFE-7000因飽和溫度較低,同條件下熱阻較FC18P低14%;FC18P則因密度較高具較佳單相熱傳能力,可作為受REACH法規限制下之潛在替代方案。
本研究冷板即便採用沸騰更劇烈之介電液,仍優於文獻水冷之接面溫度控制,且較其他HFE-7000平行式或陣列式冷板於熱阻抗與幫浦負載權衡上具優勢,佐證放射狀流道於微小鰭片間距下仍能抑制兩相流不穩定性,可為次世代高熱密度電子元件散熱設計提供參考。
As power density in computing components rises, localized hot spots have become increasingly critical, and conventional single-phase liquid cooling can no longer keep pace. Two-phase cooling using dielectric fluids has thus become a necessary trend for extending cooling limits. However, existing two-phase microchannel cold plates often suffer reverse flow and localized dryout under high heat flux, as bubbles expand rapidly within narrow channels, sharply increasing pressure drop and degrading performance. Radial jet-impingement cold plates can suppress this instability, but manufacturing precision has limited prior metal-based designs to fin spacings of about 1 mm, and most studies have used water or refrigerants rather than dielectric fluids.
In this study, three copper radial microchannel jet-impingement hybrid cold plates were fabricated via metal 3D printing, achieving a minimum fin spacing of 0.4 mm, and tested with two dielectric fluids, HFE-7000 and FC18P. The best-performing design achieved a minimum thermal resistance of 0.0231 K/W at 74.3 W/cm² using HFE-7000 (0.95 LPM, 293.15 K), reaching a maximum heat flux of 90.8 W/cm² at a junction temperature of 379.75 K. HFE-7000, with its lower saturation temperature, yielded 14% lower thermal resistance than FC18P under identical conditions, while FC18P, owing to its higher density, offered better single-phase heat transfer and serves as a potential alternative under REACH restrictions on HFE-7000.
Even with a more vigorously boiling dielectric fluid, the cold plates in this study maintained better junction temperature control than water-cooled designs reported in the literature, and showed an advantageous trade-off between thermal impedance and pumping power compared with other HFE-7000 based parallel or array-type cold plates — showing that radial channel geometry remains effective in suppressing two-phase instability even at greatly reduced fin spacing, offering a reference for thermal design of next-generation high-heat-density electronics.
In this study, three copper radial microchannel jet-impingement hybrid cold plates were fabricated via metal 3D printing, achieving a minimum fin spacing of 0.4 mm, and tested with two dielectric fluids, HFE-7000 and FC18P. The best-performing design achieved a minimum thermal resistance of 0.0231 K/W at 74.3 W/cm² using HFE-7000 (0.95 LPM, 293.15 K), reaching a maximum heat flux of 90.8 W/cm² at a junction temperature of 379.75 K. HFE-7000, with its lower saturation temperature, yielded 14% lower thermal resistance than FC18P under identical conditions, while FC18P, owing to its higher density, offered better single-phase heat transfer and serves as a potential alternative under REACH restrictions on HFE-7000.
Even with a more vigorously boiling dielectric fluid, the cold plates in this study maintained better junction temperature control than water-cooled designs reported in the literature, and showed an advantageous trade-off between thermal impedance and pumping power compared with other HFE-7000 based parallel or array-type cold plates — showing that radial channel geometry remains effective in suppressing two-phase instability even at greatly reduced fin spacing, offering a reference for thermal design of next-generation high-heat-density electronics.